Code Proposal for NEC 230.90(A) Exception 3
Sun/Apr/08
The
inspector members of the chapter voted to put forward a
proposal taken from our WAC rule 296-46B 230 40
(note incorrect WAC reference to the NEC) The proposal would modify the existing language of NEC 230.90(A) Exception No. 3 in this way:
Exception No. 3: Two to six circuit breakers or sets of fuses shall be permitted as the overcurrent device to provide the overload protection. The sum of the ratings of the circuit breakers or fuses shall be permitted to exceed the ampacity of the service conductors, provided the calculated load does not exceed the ampacity of the service conductors and the ampacity of the service entrance conductors is marked on the equipment.
Do you have any opinions about this? click on the comment link and post your thoughts
(note incorrect WAC reference to the NEC) The proposal would modify the existing language of NEC 230.90(A) Exception No. 3 in this way:
Exception No. 3: Two to six circuit breakers or sets of fuses shall be permitted as the overcurrent device to provide the overload protection. The sum of the ratings of the circuit breakers or fuses shall be permitted to exceed the ampacity of the service conductors, provided the calculated load does not exceed the ampacity of the service conductors and the ampacity of the service entrance conductors is marked on the equipment.
Do you have any opinions about this? click on the comment link and post your thoughts
|
Code Proposal for NEC 220.12 energy code lighting demands
Sun/Apr/08
The
inspector members of the chapter voted to put forward a
proposal taken from our WAC rule 296-46B 220 003
The proposal would modify the existing language of NEC 220.12 in this way:
A unit load of not less than that specified in Table 220.12 or the locally adopted energy code for occupancies specified therein shall constitute the minimum lighting load.
Do you have any opinions about this? click on the comment link and post your thoughts
The proposal would modify the existing language of NEC 220.12 in this way:
A unit load of not less than that specified in Table 220.12 or the locally adopted energy code for occupancies specified therein shall constitute the minimum lighting load.
Do you have any opinions about this? click on the comment link and post your thoughts
Code Proposal for NEC 210.52(C)(5) appliance garages
Sun/Apr/08
The
inspector members of the chapter voted to put forward a
proposal taken from our WAC rule 296-46B 051(B)5)
(note incorrect reference to NEC section in WAC) The proposal would modify the existing language of 210.52(C)(5) in this way:
5) Receptacle Outlet Location. Receptacle outlets shall be located above, but not more than 500 mm (20 in.) above, the countertop. Receptacle outlets rendered not readily accessible by appliances fastened in place, (deleted text:appliance garages), sinks, or rangetops as covered in 210.52(C)(1), Exception, or appliances occupying dedicated space shall not be considered as these required outlets.
Do you have any opinions about this? click on the comment link and post your thoughts
(note incorrect reference to NEC section in WAC) The proposal would modify the existing language of 210.52(C)(5) in this way:
5) Receptacle Outlet Location. Receptacle outlets shall be located above, but not more than 500 mm (20 in.) above, the countertop. Receptacle outlets rendered not readily accessible by appliances fastened in place, (deleted text:appliance garages), sinks, or rangetops as covered in 210.52(C)(1), Exception, or appliances occupying dedicated space shall not be considered as these required outlets.
Do you have any opinions about this? click on the comment link and post your thoughts
Code Proposal for NEC 210.8(B) GFCI wet locations
Sun/Apr/08
The
inspector members of the chapter voted to put forward a
proposal taken from our WAC rule 296-46B 210 008(B)(1)
The proposal would modify the existing language of NEC 210.8(B) in this way:
Add new: (6) Wet Locations.
Do you have any opinions about this? click on the comment link and post your thoughts
The proposal would modify the existing language of NEC 210.8(B) in this way:
Add new: (6) Wet Locations.
Do you have any opinions about this? click on the comment link and post your thoughts
Code Proposal for NEC 110.22 Identification of Disconnecting Means
Sun/Apr/08
The
inspector members of the chapter voted to put forward a
proposal taken from our WAC rule 296-46B 022(3)
The proposal would modify the existing language of 110.26 in this way:
Each disconnecting means shall be legibly marked to indicate its purpose and designation of circuit source panelboard source that supplies the disconnect, unless located and arranged so the purpose is evident.
Do you have any opinions about this? click on the comment link and post your thoughts
The proposal would modify the existing language of 110.26 in this way:
Each disconnecting means shall be legibly marked to indicate its purpose and designation of circuit source panelboard source that supplies the disconnect, unless located and arranged so the purpose is evident.
Do you have any opinions about this? click on the comment link and post your thoughts
April 12 Meeting Code Proposals
Sun/Apr/08
The April
12, 2008 Meeting was held in Forest Park at the Lions
Hall on Saturday. Christine Porter gave an IAEI
presentation on making NEC Code Proposals. The program
covered not only the mechanics of submitting proposals
but also how to create "good" proposals. The second
half of the program worked through several NEC
proposals taken from our WAC rules to be put forward
for the 2011 Edition of the NEC. These will be
forwarded on to the NW Section, to be voted on by the
section at the NW Section meeting in September.
Take a look at the proposals that were voted to be put forward.
Please note: I have not included the substantiations, just the revised, deleted, or new wording)
Take a look at the proposals that were voted to be put forward.
Please note: I have not included the substantiations, just the revised, deleted, or new wording)
January 12 2008 Meeting
Sat/Dec/07
The first
meeting in 2008 will be on Saturday, January 12. It
will be held at the Tacoma Power & Light Auditorium
located at 3628 South 35th Street in Tacoma WA. The
subject will be Grounding. Come and learn more about
the essentials of Grounding and Bonding electrical
installations from our own former Chief Electrical
Inspector, Phil Simmons.
October 13 Meeting
Thu/Oct/07
New Officers!
Sun/Jul/07
On Saturday, July 14 2007 our chapter elected a new
slate of directors and they were sworn in by Jim
Hinrichs. Our new directors are as follows:
2007/2008 Term
Officers
President - Warren Shill
1st Vice President - Clell Mason
2nd Vice President - Rand Stone
Secretary/Treasurer - Ken Copeland
Directors
Jr Past President - Dave Buttice
Inspector Member - Don Millar
Inspector Member - Bill Eckroth
Associate Member - Jim Simmons
Associate Member - Joe Andre
NW Inspector Representative - Bob Thomas
NW Associate Representative - Chris Porter
2007/2008 Term
Officers
President - Warren Shill
1st Vice President - Clell Mason
2nd Vice President - Rand Stone
Secretary/Treasurer - Ken Copeland
Directors
Jr Past President - Dave Buttice
Inspector Member - Don Millar
Inspector Member - Bill Eckroth
Associate Member - Jim Simmons
Associate Member - Joe Andre
NW Inspector Representative - Bob Thomas
NW Associate Representative - Chris Porter
Presentation by Mark Earley of NFPA
Sat/Jul/07
The July meeting was held at the new Bellevue City Hall
facility on Saturday. Mark Earley from NFPA gave two
informative presentations, one on Fire Pumps and the
second one on Hazardous Locations. Our thanks go to the
NFPA for providing the means for Mark to travel out
here to help us achieve a uniform understanding of the
NEC.
He also showed us all how to view online any NFPA Standard! To do this first, go to NFPA.org
From the menu bar just below the NFPA logo pull down the "Codes and Standards" tab to "Document list and code cycle informtion". Then click on any NFPA standard you wish to see. Scroll down to the bottom and click on the "Preview this document " link. Read the license agreement, click agree and in the new screen click on the "open" document link. You can view and read the document online, but of course you cannot cut & paste, or print the document. To do that you must purchase the document which can be done by clicking on the "online catalog" link. Here is the NFPA Web Site: NFPA.org
He also showed us all how to view online any NFPA Standard! To do this first, go to NFPA.org
From the menu bar just below the NFPA logo pull down the "Codes and Standards" tab to "Document list and code cycle informtion". Then click on any NFPA standard you wish to see. Scroll down to the bottom and click on the "Preview this document " link. Read the license agreement, click agree and in the new screen click on the "open" document link. You can view and read the document online, but of course you cannot cut & paste, or print the document. To do that you must purchase the document which can be done by clicking on the "online catalog" link. Here is the NFPA Web Site: NFPA.org
New July Meeting Location & Expo News
Sun/Jun/07
The location
for our July meeting has changed from the Issaquah Book
Depository to Bellevue City Hall. Directions can be
found here: Directions
The Electric League of the Pacific Northwest is once again hosting an electrical expo! The Northwest Energy Expo and conference in downtown Seattle will have seminars on a wide variety of topics of interest to the electrical community as well as over 200 exhibitors. Mark your calendar for October 17 and 18th!
The Electric League of the Pacific Northwest is once again hosting an electrical expo! The Northwest Energy Expo and conference in downtown Seattle will have seminars on a wide variety of topics of interest to the electrical community as well as over 200 exhibitors. Mark your calendar for October 17 and 18th!
Upcoming Elections
Sun/Apr/07
The July
meeting is our annual meeting, in addition to our
educational content we will also be electing new
directors and representatives at this meeting. If you
would like to participate let contact Ken Copeland, our
chapter secretary here.
New Feature!
Sun/Apr/07
April 14 Meeting
Sat/Apr/07
Our April
14th Meeting was held in Everett WA at the Everett
Community College. Our originally planned speaker, Mr.
Mark Earley could not make it out for the meeting due
to inclement weather so Christine Porter of Intertek
Testing Services and Warren Shill of UL gave a
presentation on NFPA 70E, Electrical Workplace Safety.
Thanks not only to them but to the active participation
by the attending members the meeting was a very
informative success. The meeting was held at Everett
Community College, 2000 Tower Street, Everett WA
98201
Map
Map
March 16 & 17 Tri Chapter
Sat/Mar/07
The Puget
Sound Chapter hosted the Tri-Chapter this year at the
Holiday Inn located at 3105 Pine Street in Everett WA.
The program consisted of an 8 hour session on Friday
that took a look at the code making process for the
2008 edition of the NEC using many of the upcoming
significant changes. It was presented by Michael
Johnston, Director of Education Codes and Standards,
IAEI. Saturday's program consisted of a 4 hour update
for the RCW/WAC rules presented by Christine Porter of
Intertek Testing Services and Tim Hingtgen of Labor
& Industries and a 2 hour session on Controversial
Code Requirements, a closer look presented by Joe Andre
of NEMA and Warren Shill of UL.
Map
Map