Think About It
NOTE: proposals to the NEC
to amend the 2011 Edition are due
Friday November 7, 2008
Below are just a very few of
the changes upcoming changes for Chapters one through four
in the 2008 Edition of the NEC. Think about these changes
and our existing codes, become a part of the consensus
based code process and help ensure that electrical
installations are essentially free from shock or fire
hazards.
Click here
to find out more
about becoming part of the process.
A new section
has been added to NEC 210.4(B) Disconnecting Means. It
requires that all multi-wire branch circuits must be
provided with a means that will simultaneously disconnect
all ungrounded conductors at the point where he branch
circuit originates. It is no longer limited to only those
multi-wire branch circuits that terminate on a single yoke.
The requirements for GFCI protection of the 15 or 20 Amp,
125V receptacles have been revised in both the dwelling
unit and the non-dwelling unit sections. Generally, the
exceptions that used to allow receptacles in areas like
unfinished basements or garages of dwelling units to not
have GFCI protection have been eliminated. Expansion of the
GFCI requirement in other than dwelling units has also
occurred with the new requirements for protection of
receptacles generally located within 6' of sinks in other
than dwelling units. (there are still some specific
exemptions such as for Industrial Facilities, Industrial
Laboratories, and Health Care Facilities)
The requirements for AFCI protection has been expanded to
include all the 15 or 20 Amp, 120V, single phase branch
circuits that supply outlets in dwelling unit family rooms,
living rooms, dining rooms, parlors, libraries, dens,
bedrooms, sunrooms, recreation rooms, closets, hallways or
similar rooms or areas. Also, the 6' limitation on the
metallic cable or raceway to a first AFCI device in the
former exception has been removed.
NEC 250.94 has been extensively revised to generally now
require an accessible means for the bonding of other
systems (CATV, Dish, Broadband, etc) that is permanent and
has the capacity for not less than 3 intersystem bonding
conductors.
NEC 300.4 has been revised, and a new (E) covers the
protection for cables under Roof Decks, requiring either
that the cables be located 38 mm (1-1/2") from the nearest
surface of the decking or be encased in types RMC or IMC
raceways.
NEC 310.15(B)(2) has a new subdivision (c). It is a new
table for adjusting the allowable ampacities of conductors
in conduits located where exposed to sunlight on or above
rooftops.
NEC 334.80 has been revised to clarify that the exceptions
in 310.15(B)(2)(a) do not apply when installing cables
through holes that are fire-stopped or draft-stopped,
caulked, or sealed with foam. It also now includes cables
that are installed in contact with thermal insulation
without maintaining spacings.
NEC 406.11 now requires listed Tamper Resistant style
receptacles for dwelling unit 15A and 20A, 120V single
phase receptacles specified in 210.52
NEC 408.36 has been revised to remove the definition of
Lighting and Appliance branch circuit panelboards and Power
panelboards. It also has generally deleted the limitation
on the maximum number of overcurrent devices permitted in a
panelboard.